Use
Local Operation on the UMI
Operating Functions not Requiring a
Password
Resetting Latched Information
Press this button to reset latched information. Sepam™ reset must be confirmed.
The alarm messages are not erased.
Acknowledging the Active Alarm
When Sepam™ displays an alarm, this button returns the user to the screen
displayed prior to the alarm or to a less recent unacknowledged alarm. Itdoes not
reset latched information.
Reset the Peak Demand Measurements
The Sepam™ UMI can reset the following measurement and diagnosis information:
b demand current
b peak demand current
b peak demand power
Use the following steps to reset information:
1 Display the screen showing the information to be reset.
2 Press the reset button.
Clearing the Alarm History
Sepam™ stores the history of the last 16 alarms. To clear this information perform
the following steps:
1 Press this button to display the alarm history.
2 Press the clear button to clear the alarm history.
Testing LEDs and Display
To check the LEDs and each pixel in the display, press this button for five seconds.
The nine LEDs go on successively in a predefined sequence. The pixels in the
display will light in a predefined sequence.