Commissioning
Methods
General Principles
1 Conduct all tests with the MV cubicle completely isolated and the MV circuit
breaker racked out (disconnected and open)
2 Perform all tests in the operating situation: no wiring or setting changes,
even temporary changes to facilitate testing, are allowed.
The SFT2841 parameter setting and operating software is the basic tool for Sepam™
users. It is especially useful during Sepam™ commissioning tests. The tests
described in this document are based on the systematic use of this tool. You can
perform the commissioning tests without the SFT2841 software for Sepam™ units
with advanced UMIs.
For each Sepam™:
b only carry out the checks suited to the hardware configuration and the
functions activated
b use the test sheet provided to record the results of the commissioning tests
A comprehensive description of all the tests is given later.
Checking Current and Voltage Input Connections
Factors affecting secondary injection tests include, but are not limited to:
b the type of current and voltage sensors connected to Sepam™ for residual
current and voltage measurement
b the type of injection generator used for the tests: three-phase or single-phase
generator
b the type of Sepam™
These tests check the current and voltage input connections. The descriptions below
also include:
b a detailed test procedure
b the connection diagram of the associated test generator
Determining Checks to Conduct
The table below indicates the page on which the following are described:
b general tests performed according to the type of measurement sensors and
type of generator used
b additional tests performed for certain types of Sepam™ having a single or
three-phase generator
General Tests
Current Sensors Voltage Sensors Three-Phase
Generator
Single-Phase
Generator
3 CTs or 3 LPCTs 3 VTs page 122 page 124
3 CTs or 3 LPCTs
1 or 2 core bal. CTs
3 VTs page 122
page 129
page 124
page 129
3 CTs or 3 LPCTs 3 VTs
3 V0 VTs
page 122
page 130
page 124
page 130
3 CTs or 3 LPCTs
1 or 2 core bal. CTs
3 VTs
3 Vr VTs
page 122
page 128
page 124
page 128
3 CTs or 3 LPCTs 2 phase VTs
3 Vr VTs
page 123
pag e 1 30
page 125
page 130
3 CTs or 3 LPCTs
1 or 2 zero
sequencezero
sequence CTs
2 phase VTs
3 Vr VTs
page 123
page 128
page 125
page 128
3 CTs or 3 LPCTs 3 VTs
1 neutral point VT
page 122
page 131
page 124
page 131
3 CTs or 3 LPCTs
1 or 2 core bal. CTs
3 VTs
1 neutral point VT
page 122
pages 129 and 131
page 124
pages 129 and 131
3 CTs or 3 LPCTs 2 phase VTs
1 neutral point VT
page 123
page 131
page 125
page 131
3 CTs or 3 LPCTs
1 or 2 core bal. CTs
2 phase VTs
1 neutral point VT
page 123
pages 129 and 131
page 125
pages 129 and 131
Additional Tests
Type of Sepam™ Type of Test
T87,
M87, M88,
G87, G88
Phase current input connections
for differential application
page 126
B80 Additional phase voltage input connection page 132
B83 Additional phase voltage input connections page 134
B83 Additional residual voltage input connection page 134
C86 Unbalance current input connections page 137