© 2007 Schneider Electric. All Rights Reserved.63230-216-229-B1
Commissioning
Required Testing and Metering
Equipment
Generators
The AC and DC Generators have the following characteristics:
b dual sinusoidal AC current and voltage generator:
v 50 or 60 Hz frequency (according to the country)
v current adjustable up to at least 5 A rms
v adjustable up to the rated secondary phase-to-phase voltage of the VTs
v adjustable relative phase displacement (V, I)
v three-phase or single-phase type
b DC voltage generator:
v adjustable from 48 to 250 V DC, for adaptation to the voltage level of the
logic input being tested
Accessories
The following accessories come with the metering and testing equipment:
b plug with cord to match the "current" test terminal box installed
b plug with cord to match the "voltage" test terminal box installed
b electric cord with clamps, wire grip or touch probes
Metering Devices (part of the generator or separate)
b 1 ammeter, 0 to 5 A rms
b 1 voltmeter, 0 to 230 V rms
b 1 phasemeter, if phase displacement (V, I) is not identified on the voltage and
current generator
Computer Equipment
b PC with minimal configuration:
v Microsoft Windows 98 / NT4.0 / 2000 / XP
v 133 MHz Pentium processor
v 64 MB of RAM (32 MB with Windows 98)
v 64 MB free on hard disk
v CD-ROM drive
v One serieal port (or USB port with serial converter)
b SFT2841 software
b CCA783 serial connection cord between the PC and Sepam™
Documents
b complete connection diagram of Sepam™ and additional modules, with:
v phase current input connections to the corresponding CTs via the test
terminal box
v residual current input connection
v phase voltage input connections to the corresponding VTs via the test
terminal box
v
residual voltage input connection to the corresponding VTs via the test
terminal box
v logic input and output connections
v temperature sensor connections
v analog output connection
v connection of the sync-check module
b hardware bill-of-materials (BOMs) and installation rules
b group of Sepam™ parameter and protection settings, available in paper format