LPCT Type Current Sensors
Function
Low Power Current Transducer (LPCT) type sensors are voltage-output sensors that
comply with IEC 60044-8.
The Square D range of LPCTs includes the following sensors:
CLP1
CLP2
CLP3
TLP160
TLP190.
CCA671 Connector
CCA671-1
Function
Three LPCT sensors connect to the CCA671 on the rear panel of Sepam™. The
CCA671 changes inputs from the LPCTs into a low level signal scale based on the
Full Load Amps (FLA) for each phase.
Description
1 There are three blocks of microswitches that set the CCA671 to the rated phase
current value.
2 Microswitch setting/selected rated current equivalency table (two In values per
position).
3 There are three RJ45 radial plugs to connect the LPCT sensors.
4 9-pin sub-D connector to connect test equipment (ACE917 for direct connector
or via CCA613).
Rating
The CCA671 connector is rated according by the rated primary current IN, and
measured by the LPCT sensors. IN is the current value that corresponds to the rated
secondary current of 22.5 mV. The possible settings for IN (in amps) are: 25, 50, 100,
125, 133, 200, 250, 320, 400, 500, 630, 666, 1000, 1600, 2000, 3150.
The selected IN value should be:
b entered as a Sepam™ general setting
and
b configured by microswitch on the CCA670/CCA671 connector.
Operating Mode:
1 Use a screwdriver to remove the shield located in the "LPCT settings" zone; the
shield protects three blocks of eight microswitches marked L1, L2, L3.
2 On the L1 block, set the microswitch for the selected rated current to "1" (two IN
values per microswitch).
b The table of equivalencies between the microswitch settings and the selected
rated current I
N is printed on the connector
b Leave the other microswitches set to "0"
3 Set the other two blocks of switches L2 and L3 to the same position as the L1
block and close the shield.
Radial plugs for Sepam™ Series 80 (item 3)
CAUTION
HAZARD OF NON-OPERATION
b Set the microswitches for the CCA671
connector before commissioning the
device.
b Check that only one microswitch is in
position 1 for each block L1, L2, L3, and
that no microswitch is in the center
position.
b Check that the microswitch settings on all
three blocks are identical.
Sepam™ will go into a fail-safe mode if all
three LPCT sensors are not connected.
Failure to follow these instructions can cause
incorrect operation.
1
2
3
4