10763230-216-229-B1
2
© 2007 Schneider Electric. All Rights Reserved.
Use
SFT2841 Software
Mimic-Diagram Editor
Presentation
Description
SFT2841 Sepam™ setting and operating software includes a mimic-diagram editor
you can use to personalize the mimic diagram for local control on the mimic-based
UMI of Sepam™ Series 80 units.
A mimic-diagram or single-line diagram is a simplified diagram of an electrical
installation. It is made up of a fixed background on which symbols and
measurements are placed.
The mimic-diagram editor can be used to:
b create a fixed bitmap background (128 x 240 pixels) using standard drawing
software
b create animated symbols or use predefined animated symbols to represent
the electrotechnical devices or other objects
b assign the logic inputs or internal status conditions that modify the animated
symbols. For example, the logic inputs for the circuit-breaker position must be
assigned to the circuit-breaker symbol to enable the display of the open and
closed conditions
b assign the logic outputs or internal status conditions that activate when
opening or closing commands are issued for the symbol
b display current, voltage, and power measurements on the mimic diagram
Mimic-Diagram and Symbols
The symbols making up the mimic-diagram constitute the interface between the
mimic-based UMI and other Sepam™ control functions.
There are three types of symbols:
b A Fixed symbol: represents the electrotechnical devices that are neither
animated or controlled such as a transformer
b An Animated symbol: with one or two inputs represents the electrotechnical
devices that change on the mimic diagram, depending on the symbol inputs,
but cannot be controlled via the Sepam™ mimic-based UMI.
This type of symbol is used for switch-disconnectors without remote controls.
b A Controlled symbol: with one or two inputs/outputs represents the
electrotechnical devices that change on the mimic diagram, depending on the
symbol inputs, and can be controlled via the Sepam™ mimic-based UMI. This
type of symbol is used for circuit breakers
The symbol outputs are used to control the electrotechnical device:
v directly via the Sepam™ logic outputs
v by the switchgear control function
v by logic equations or the Logipam program
Local Control using Symbols
Controlled - 1 input/output and Controlled - 2 input/output symbols are used to
control the switchgear that corresponds to the symbol via the Sepam™ mimic-based
UMI.
Control Symbols with One Output
Controlled - 1 input/output symbols have one control output. The output remains
in the last state to which it was commanded.
A new command causes in a change in the output state.
Control Symbols with Two Outputs
Controlled - 2 input/output symbols have two control outputs for opening and
closing of the symbolized device. A command on the mimic-based UMI sends a 300
ms pulse on the controlled output.
Blocking Commands
Controlled - 1 input/output and Controlled - 2 input/output symbols have two
blocking inputs that block opening and closing commands when set to "1". This
makes it possible to create interlocking systems or other command-disabling
systems that the UMI takes into account.