45
1
© 2007 Schneider Electric. All Rights Reserved.
63230-216-229-B1
Installation
MES120, MES120G, MES120H
14 Input/6 Output Modules
Installation
DE80078
Description
There are three removable, lockable screw-type connectors.
1 20-pin connector for nine logic inputs:
b Ix01 to Ix04: four independent logic inputs
b Ix05 to Ix09: five common point logic inputs
2 7-pin connector for five common point logic inputs Ix10 to Ix14.
3 17-pin connector for six relay outputs:
b Ox01: one control relay output
b Ox02 to Ox06: five annunciation relay outputs.
Addressing of MES120 module inputs / outputs:
b x = 1 for the module connected to H1
b x = 2 for the module connected to H2
b x = 3 for the module connected to H3.
4 MES120G, MES120H identification label (MES120 modules have no labels).
Installation of the second MES120 module, connected to base
unit connector H2
Assembly
PE50026
Installation of an MES120 Module on the Base Unit
1 Insert the two pins on the MES module into the slots (1) on the base unit.
2 Push the module flat up against the base unit to plug it into the connector (H2).
3 Partially tighten the two mounting screws (2) before locking them.
4 For the MES120, if only one module is required, connect it to connector (H1) as shown.
5 If two modules are required, connect them to connectors (H1) and (H2).
6 If three modules are required (maximum configuration), the three connectors H1, H2 and
H3 are used.