Installation
LPCT Type Current Sensors
Test Accessories
ACE917 Injection Adapter
Function
The ACE917 adapter is used to test the protection chain with a standard injection box
when Sepam™ is connected to LPCT sensors.
The ACE917 adapter is inserted between:
b the standard injection box
b the LPCT test plug is either:
v integrated in the Sepam™ CCA671 interface connector
v transferred by means of the CCA613 accessory
The following are supplied with the ACE917 injection adapter:
b power supply cord
b 3-meter (9.8 ft) cord to connect the ACE917 to the LPCT test plug on
CCA671 or CCA613
DE80065
Characteristics
Power supply 115/230 V AC
Protection by time-delayed fuse 5 mm x 20 mm
(0.2 x 0.79 in)
0.25 A rating
CCA613 Remote Test Plug
Function
The CCA613 test plug flush-mounts on the front of the cubicle. It has a 3-meter
(9.8 ft) cord that transfers data from the test plug integrated in the CCA671 interface
connector on the rear panel of Sepam™.
Dimensions
DE80045
DE80046
Front view with cover lifted Right side view
DE80047
Cut-out
in.
(mm)
(260)
10.24
(170)
6.69
(70)
2.76
in.
(mm)
(44)
1.73
(67.5)
2.66
Mounting lug
Cable
(13)
0.51
(80)
3.15
(50)
1.97
(67.5)
2.66
in.
(mm)