Use
SFT2841 Setting and Operating
Software
Setting Up and Operating a Logipam
Program
PE50429
Presentation
The Logipam screen in the SFT2841 software is used to:
b link a Logipam program to the configuration of a Sepam™
b set program parameters
b view the internal program variables to assist in program set-up
Note: Use the SFT2885 software to first enter and confirm Logipam.
Press to access the Logipam screen.
The Logipam screen is accessed in Connected mode with a Sepam™ if it has the
Logipam SFT080 option. In disconnected mode, the Logipam screen is still
accessible, but the configuration files containing a Logipam program are loaded
exclusively to Sepam™ units with the SFT080 option.
The Logipam screen has five tabs:
b Logipam: selection of the program and its operating mode
b Internal bits: view the internal bits and set the configuration bits
b Counters: view the current value and set the counters
b Delays: set time delays
b Clocks: set the clocks
Linking Logipam to a Sepam™ Configuration
Logipam links to a Sepam™ configuration by selecting the program file. Use the
Select button on the Logipam tab sheet.
The programs are stored in the Logipam subdirectory of the SFT2841 installation
directory (by default C:\Program Files\Schneider\SFT2841\Logipam). They have the
extension *.bin.
Once the program has been selected, the program properties display (name,
version, author, installation characteristics, etc.).
The "Apply" Button
In Disconnected mode, the Apply button stores the name of the Logipam program
in the Sepam™ configuration file. The program is then loaded in Sepam™ at the
same time as the configuration file.
In Connected mode, it stores the name of the Logipam program in the Sepam™
configuration file and loads the program in Sepam™.
The Delete Button
The Delete button eliminates the link between the Logipam program and the
configuration file. In Connected mode, the name of the Logipam program is deleted
in the Sepam™ memory cartridge when the Apply button is clicked.
Selecting the operating mode of Logipam:
b On: the program runs immediately after it is loaded
b Off: the program does not run and program outputs remain set to 0
You can also temporarily postpone Logipam program processing if the program has
not been fully set up.