Installation
ACE9492
2-Wire RS485 Network Interface
Function
PE50029
The ACE9492 interface performs two functions:
b It provides an electrical interface between Sepam™ and a two-wire RS485
communication network
b It is the main network cable branching box that connects Sepam™ with a
CCA612 cord
Characteristics
ACE9492 Module
Weight 0.1 kg (0.22 lb.)
ACE9492 two-wire RS485 network connection interface Assembly On symmetrical DIN rail
Operating temperature –25°C to +70°C (–13°F to +158°F)
Environmental characteristics Same characteristics as Sepam™ base units
Two-Wire RS485 Electrical Interface
Standard EIA 2-wire RS485 differential
Distributed power supply External, 12 V DC or 24 V DC ±10%
Power burden 16 mA in receiving mode
40 mA maximum in sending mode
Maximum Length of Two-Wire RS485 Network
with Standard Cable
DE80035
Number of
Sepam™ Units
Maximum Length with
12 V DC Power Supply
Maximum Length with
24 V DC Power Supply
5 1000 ft. (320 m) 3300 ft (1000 m)
10 590 ft (180 m) 2500 ft (750 m)
20 520 ft (160 m) 1500 ft (450 m)
25 410 ft (125 m) 1200 ft (375 m)
Description and Dimensions
and Terminal blocks for network cable
RJ45 socket to connect the interface to the base unit with a CCA612 cord
Grounding terminal
1 The Link Activity LED flashes when active communication occurs (sending or
receiving is in progress).
2 The jumper for RS485 network line-end impedance matching with load resistor
(Rc = 150 Ω), is set to:
b , if the module is not at one end of the network (default position). The "X"
over the "Rc" indicates that the resistor is not in use.
b Rc, if the module is at one end of the network. This means the resistor is
jumpered in.
3 Network cable clamps
(inner diameter of clamp = 6 mm or 0.24 in).
(1) 2.8 in (70 mm) with CCA612 cord connected
DE80127
Connection
1 Connect the network cable to screw-type terminal blocks and
2 Connect the ground terminal by tinned copper braid with cross-section ≥ 6 mm²
(AWG 10), or cable with cross-section ≥ 2.5 mm² (AWG 12), and length ≤ 200
mm (7.9 in), fitted with a 4 mm (0.16 in) ring lug.
3 Check the tightness. The maximum tightening torque is 19.5 in-lb (2.2 Nm).
4 The interfaces are fitted with clamps to hold the network cable and recover
shielding at the incoming and outgoing points of the network cable:
b The network cable must be stripped
b The cable shielding braid must physically contact (and wrap around) the clamp
5 Use a CCA612 cord (length = 9.8 feet, or 3 m, with green fittings) to connect the
interface to connector on the base unit
6 Supply 12 V DC or 24 V DC to the interfaces
Note : The cable shielding shown at left should only be done at one point, preferably at one end
of the daisy chain.
2.83
(72)
3.46
(88)
in.
(mm)
(30)
(1)
1.18
No
termination
2-wire
2-wire
network
network
Power supply
Power supply
or
or
24 V DC
24 V DC
No
termination