Black Box IC109A-R2 Manual de instalación Pagina 42

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 164
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 41
36
© 2007 Schneider Electric. All Rights Reserved.
1
63230-216-229-B1
Installation
CSH120 & CSH200
Zero Sequence CT
Function
PE50032
The specifically designed CSH120 and CSH200 zero sequence CTs measure direct
residual current. The only difference between them is the diameter. Due to their low
voltage insulation, they are used only on cables.
Characteristics
CSH120 CSH200
Inner diameter 120 mm (4.7 in) 200 mm (7.9 in)
Weight 0.6 kg (1.32 lb) 1.4 kg (3.09 lb)
Accuracy ±5% at 20°C (68°F)
±6% max. from –25°C to 70°C
(–13°F to +158°F)
Transformation ratio 1/470
CSH120 and CSH200 Zero Sequence CTs. Maximum permissible current 20 kA - 1 s
Operating temperature –25°C to +70°C (–13°F to +158°F)
Storage temperature –40°C to +85°C (–40°F to +185°F)
Dimensions
DE10228
Dimensions A B D E F H J K L
CSH120
(i
N)
120
(4.75)
164
(6.46)
44
(1.73)
190
(7.48)
76
(2.99)
40
(1.57)
166
(6.54)
62
(2.44)
35
(1.38)
CSH200
(i
N)
200
(7.87)
256
(10.1)
46
(1.81)
274
(10.8)
120
(4.72)
60
(2.36)
257
(10.1)
104
(4.09)
37
(1.46)
4 horizontal mounting
holes Ø 0.2 in. (5 mm)
4 vertical mounting
holes Ø 0.2 in. (5 mm)
Vista de pagina 41
1 2 ... 37 38 39 40 41 42 43 44 45 46 47 ... 163 164

Comentarios a estos manuales

Sin comentarios