Installation
Voltage Transformers
DANGER
Assembly
1 Insert the three connector pins into the slots on the
base unit.
2 Rotate connector to plug it into the 9-pin SUB-D
connector
3 Tighten the mounting screw .
HAZARD OF ELECTRIC SHOCK, EXPLOSION,
OR ARC FLASH
b Only qualified electrical workers should
install this equipment. Such work should
be performed only after reading this entire
set of instructions.
b NEVER work alone.
b Before performing visual inspections, tests,
or maintenance on this equipment,
disconnect all sources of electric power.
Assume that all circuits are live until they
have been completely de-energized,
tested, and tagged. Pay particular
attention to the design of the power
system. Consider all sources of power,
including the possibility of backfeeding.
b Always use a properly rated voltage
sensing device to confirm that all power is
off.
b Start by connecting the device to the
protective ground and to the functional
ground.
b Tighten all terminal screws, even those not
in use.
Failure to follow these instructions will result
in death or serious injury.
DE80104
DE80105
Connection
Make the connections to the screw-type connectors on the rear panel of the CCT640
(item above).
Wiring without Fittings
b One wire with maximum cross-section 0.2 to 2.5 mm² (
≤• AWG 24-12) or two
wires with maximum cross-section 0.2 to 1 mm² (
AWG 24-16)
b Stripped length: 8 to 10 mm (0.31 to 0.39 in)
Wiring with Fittings
Recommended wiring with Telemecanique fittings:
b DZ5CE015D for one 1.5 mm² wire (AWG 16)
b DZ5CE025D for one 2.5 mm² wire (AWG 12)
b AZ5DE010D for two 1 mm² wires (AWG 18)
b Tube length: 8.2 mm (0.32 in)
b Stripped length: 8 mm (0.31 in)
b Tightening torque: 6.1 to 8.8 in-lb (0.7 to 1 Nm)
Grounding
The CCT640 must be grounded by connection (green/yellow wire and ring lug) to the
screw This is a safety measure in case the CCT640 disconnects.
* Detection of Plugged Connector (required for proper operation. Installed manually)
1
2
c
b
a
V‘cn
V‘bn
V‘an
V‘r
3
4