Chapter 4 Runtime Operation
4-4 3BUR 001 085R0001 REV A
Redundancy
No provisions are made to directly support any smart device vendors specific redundancy
scheme. The redundant port can be any other port in the Advant Controller CPU. When the
Advant smart device interface loses communications with the primary port and the backup port
is “communicating”, then a swap to the backup port is performed. Loss of communications is
determined by a predefined set of error conditions. The MVI automatically performs
communications testing to the configured smart devices on a given port, the application need
only check the status word in the MOD300 database for the current state of the backup port.
Error Conditions
The following is a list of error conditions which will cause the Advant smart device Interface to
attempt a swap to the backup communications port.
Link down,
Board Unavailable.
4.2.2 Start-up
During start-up from SSE the Advant Smart Device (Hart) Interface examines the MOD300
database to see if it has been defined. If it has, it creates any additional buffers it might need then
starts the scanner, transmitter, receiver, momentary output, request output, backup monitor and
diagnostic input tasks. It also will signal CCF that it has completed its start-up and one full scan
of data. If it is not defined it will signal CCF that it is complete and does not exist.
4.2.2.1 Coordination Signals
The Serial Interface will not allow commands to be processed by it until it has sent
configuration data to the MVI board. So the interface must check the MOD300 database to
verify the status of the port before attempting any outputs. CCF must also wait, but it waits for
the smart device interface to complete one full scan and update all the data tables before
continuing processing. If the MVI can not be configured or a scan completed then CCF is
signalled to continue but with bad data quality for all smart device points. The time before the
bad data quality is set is a user configurable function (Good Data Wait).
4.2.2.2 Scanner Task
The scanner processes each smart device on every port and requests the configured data. The
scanner runs at a user configurable base rate and requests data at the segment’s configured scan
rate, a multiple of the base rate. The request goes to the end of the transmitter output queue for
output to the device. If the segment is a Scan Complete Acknowledge it is processed in one of
two ways. If the segment’s scan rate is zero then the command is sent after the READ command
with the longest scan rate, or if it is a non-zero value then the command will go out at that given
scan rate like a READ command. Note: if there are no read commands, which must have a scan
rate, then the SCA must have a scan rate.