) Interface User’s Guide
Section 3.3.5 Configuration of Smart Device (PLC) Parameters
3BUR 001 085R0001 REV A 3-25
MAX ANALOG GROUP
This is the maximum window size for attempting to create an analog group output command to
the smart device.
Use the List function key (<F4>) to list the possible analog sizes. Use the Up Arrow or Down
Arrow keys to highlight the value wanted, then press the Accept function key (<F8>) to enter
the value in the field.
The initial default value is 16.
The possible values are:
4
8 <- used for SHIMs
16
32
64
96
128
SWITCH STATION ADDR
This will define whether there will be a switch of station address when there is a swap of serial
ports.
Use the List function key (<F4>) to list the possible action of SWITCH STATION. Use the Up
Arrow or Down Arrow keys to highlight the value wanted, then press the Accept function key
(<F8>) to enter the value in the field.
The initial default value is NO.
The possible values are:
NO <- used for SHIMs
YES
COMMAND SET
This templet names the commands for the type of smart device attached to the port. The
acceptable smart device types are defined in the PLC_CMDS reference templets that are defined
as part of the PLC_DIR of the Advant OCS data base. Please see Section A.1.1, PLC_AB Initial
Data Base, Section A.1.2, PLC_MODBUS Initial Data Base, and Section A.1.3,
PLC_COMMON Initial Data Base for more information on the reference templets.
Acceptable PLC_CMDS are:
•PLC_AB
• PLC_MODBUS <- used for SHIMs
• PLC_COMMON