Advant
®
Smart Device (HART
®
) Interface User’s Guide
Section 5.4.1 User Repair
3BUR 001 085R0001 REV A 5-5
10. Ensure that the board contacts mate properly with the contacts in the rear plane and screw
the locking mechanism in place.
11. Boards which can be replaced during operations are initialized automatically by the system
and the fault indicating LED extinguishes automatically after approximately 10 seconds.
12. Perform a function test on the new board.
Additional Aspects on Individual Board Types
Table 5-1 lists AC460 subrack boards (applied in the controller subrack). Descriptions of these
types are referred individually in the table.
The S100 I/O boards are described in the S100 I/O User’s Guide.
5.4.1.2 Smart Device Removal and Installation Procedures
Smart Device Removal
To remove a smart device for servicing or replacement, disconnect all field wiring from the
smart device at the screw terminations on the analog termination panel if connected to one, the
SHIM, and the smart device itself.
Table 5-1. Replacement Aspects on Boards in the Controller Subrack
Board Type - Jumpering Comments
CI532V02
MVI
Submodule
No operational jumpering on module S1
used for testing (no jumpers).
X6 is a debug communications port
used for testing.
- Replacement with power applied is possible.
- Described in:
Advant Controller 410 and 460
User’s Guides
-May affect serial I/O communication with
device.
SC510
COMM 1
No jumpering - Replacement with power applied is possible.
S1
1
2
3
4
1
2
X6
X5
X4
Comentarios a estos manuales