Advant
®
Smart Device (HART
®
) Interface User’s Guide
Chapter 5 Maintenance
5-2 3BUR 001 085R0001 REV A
housing is illuminated if a RAM error is detected, and the other LED is illuminated if a ROM
checksum error is detected. If the LED on the front panel is not flashing and either of the other
LEDs is illuminated, the SHIM is not operational and should be replaced.
5.3 Error Messages
This section explains error codes returned by the Smart Device Interface to the Advant OCS
System and reported as diagnostic messages on the Diagnostic Message Display.
5.3.1 Diagnostic Messages
As a benefit of the Smart Device Interface, you can continuously receive diagnostic information
from smart devices in the field via digital communications when reading the primary value. This
information is not provided with standard analog processing.
Diagnostic information retrieved from the smart device is incorporated into the Advant OCS
Diagnostic Package with details indicating which device generated the error and its logical
location in the field (that is, the Advant Controller (MVI) serial port and SHIM network
address).
The following examples show the format of the diagnostic messages generated for SHIMs:
SMART NETWORK 2 FAILED TO RESPOND ON PORT 5
SMART NETWORK 2 HAS RESUMED COMMUNICATION
The first message is generated when the wiring between the serial I/O port and SHIM is
disconnected, severing communication with the SHIM and all smart devices connected to that
SHIM. The second message is generated when the physical connection between the serial I/O
port and SHIM is re-established, resuming communication with the SHIM and all smart devices
connected to that SHIM.
Both of these messages have 2 digits reserved for identifying the network address (1-31) of the
SHIM that failed or resumed communication. The first message also has 2 digits reserved for
identifying the serial I/O port to which the SHIM is connected. This allows you to easily locate
the SHIM in field and correct the problem.
The following is an example of a communication error code returned by a SHIM:
SDI: ERROR 1 RECEIVING MSG FROM NETWORK 5
The first number in the error message indicates a communication error, and the second number
identifies the SHIM’s network address where the communication error occurred.
The following examples show the format of the diagnostic messages generated for smart
devices:
SMART DEV 201 FAILED TO RESPOND ON PORT 5
SMART DEV 201 HAS RESUMED COMMUNICATION
SMART DEV 201 SENT ERROR CODE 2
The first message is generated when the wiring between the smart device and SHIM is
disconnected, severing communication with the smart device. The second message is generated
when the physical connection between the smart device and SHIM is re-established, resuming