Vista de pagina 39
Advant
®
Smart Device (HART
®
) Interface User’s Guide
Chapter 2 Installation
2-28 3BUR 001 085R0001 REV A
S800 I/O
Analog signals brought into an Advant Controller employing S800 I/O use either AI810 Analog
Input modules or AI820 Analog Input modules. The AI810 module has terminations for 8
analog inputs, and the AI820 has terminations for 4 analog inputs.
To communicate information from the S800 I/O modules to the Advant Controller, a CI520
Advant Fieldbus 100 (AF 100) submodule is required. The CI520 has connections to the Advant
Fieldbus 100 modem that connects to the S800 I/O Stations. Up to 32 I/O Stations can be
configured on one AF 100 segment and each S800 I/O Station can have up to 24 I/O modules.
Please refer to the S800 I/O User’s Guide, Advant Fieldbus 100 User’s Guide, Advant
Controller 410 User’s Guide and the Advant Controller 460 User’s Guide for more information
on S800 I/O connections.