Section 2.3.1 Connecting to a SHIM
3BUR 001 085R0001 REV A 2-21
You can purchase SHIMs with their ModbusB slave addresses preset by ABB. The preset
address is indicated on a sticker on the side of the SHIM’s housing, thereby, allowing you to
easily locate a particular SHIM in the field. If you purchased SHIMs without preset ModbusB
slave addresses or you want to change a SHIM’s address, set switch positions S1-1 through S1-
5 to the ON or OFF setting that produces the desired address and write the address on the sticker
on the side of the SHIM housing. For example, to set a SHIM’s ModbusB slave address to 2,
switch positions S1-1 through S1-5 are set to OFF, ON, OFF, OFF, and OFF, respectively. The
SHIM in Figure 2-16 has a ModbusB slave address of 2.
2.3.1.4 Setting SHIM Parity and Baud Rate
HART protocol communicates smart device field data to the SHIM at 1200 baud, and ModbusB
protocol communicates at 9600 baud. Therefore, to support ModbusB protocol for the
communication of smart device field data to the Advant Controller, SHIM serial ports are
configured at 9600 baud with no parity by default. The SHIM serial port baud rate and parity are
Figure 2-16. DIP Switches Accessible from Back Panel of SHIM
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
S1
S2