Black Box SW980A Manual de usuario

Busca en linea o descarga Manual de usuario para Los conmutadores de red Black Box SW980A. Black Box SW980A Product data [en] Manual de usuario

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 42
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 0
Created 03/04/2009
Edited and/or Printed 04/10/2014
282601 - 1 Project No. 44611-E
SECTION 282601
PERSONAL ALARM SYSTEMS (PAS)
PART 1 GENERAL
1.01 RELATED WORK FURNISHED BY OTHERS
A. PAS equipment is being installed under other State contracts, all work required by this
contract will be required to coordinated with the work of the other State contracts.
B. Certain services and materials identified as “(Provided or Furnished by Others)” in this
specification section are to be purchased by the owner through the State contracts.
1. The services being provided by others are identified in PART 1 of this specification
section.
a. Coordinate and schedule the performance of these services with the Director's
Representative so that they are performed to coincide with performance of the
work required by this contract.
2. The materials being provided or furnished by others are identified in PART 2 of this
specification section.
a. These materials are to be installed as part of the work required by this contract.
Contractors shall include the cost of the labor to install these materials in their
bid amount.
b. Coordinate and schedule the delivery of these materials with the Director's
Representative so that the materials are delivered prior to (or coinciding with)
when they are to be installed.
c. Coordinate the exact placement of these materials with the state contractor and
Director's Representative.
3. Unless clearly identified as “(Furnished or Provided by Others)” in this specification
section, Contractors shall include the cost for all work (materials, services, installation,
etc.) in their bid amount.
1.02 RELATED WORK SPECIFIED ELSEWHERE
A. Firestopping: 078400.
1.03 REFERENCES
A. Underwriters Laboratories Inc.
B. National Electrical Code (NEC)
1.04 DEFINITIONS:
A. Provide: Deliver to the project site all required equipment and accessories, install and
interconnect all required equipment and accessories for a complete and operational
system.
B. Furnished: Equipment or support systems delivered to site by others.
Vista de pagina 0
1 2 3 4 5 6 ... 41 42

Indice de contenidos

Pagina 1 - Created 03/04/2009

Created 03/04/2009 Edited and/or Printed 04/10/2014 282601 - 1 Project No. 44611-E SECTION 282601 PERSONAL ALARM SYSTEMS (PAS) PART 1 GENERAL

Pagina 2

Created 03/04/2009 Edited and/or Printed 04/10/2014 282601 - 10 Project No. 44611-E C. Electronic circuitry for the Multiplex Receiver shall be co

Pagina 3

Created 03/04/2009 Edited and/or Printed 04/10/2014 282601 - 11 Project No. 44611-E H. MAKE: Bosch Security Systems EA120B. 2.05 CHIMES (PROVID

Pagina 4

Created 03/04/2009 Edited and/or Printed 04/10/2014 282601 - 12 Project No. 44611-E alarms. Further, the Transponder shall activate the sounders and

Pagina 5

Created 03/04/2009 Edited and/or Printed 04/10/2014 282601 - 13 Project No. 44611-E B. The cover shall secure to the enclosure using a keyed lock.

Pagina 6

Created 03/04/2009 Edited and/or Printed 04/10/2014 282601 - 14 Project No. 44611-E K. The Security Escort(R) Application Software shall different

Pagina 7

Created 03/04/2009 Edited and/or Printed 04/10/2014 282601 - 15 Project No. 44611-E 2.11 APPLICATION SOFTWARE (FURNISHED BY TYCO) A. System Soft

Pagina 8

Created 03/04/2009 Edited and/or Printed 04/10/2014 282601 - 16 Project No. 44611-E driven cursor anywhere on the map display and, by pressing a but

Pagina 9

Created 03/04/2009 Edited and/or Printed 04/10/2014 282601 - 17 Project No. 44611-E 2.16 ALARM ZONE MAPS (PROVIDED BY TYCO) A. Alarm zone maps sh

Pagina 10

Created 03/04/2009 Edited and/or Printed 04/10/2014 282601 - 18 Project No. 44611-E PART 3 EXECUTION 3.01 INTERRUPTIONS TO EXISTING SYSTEM A. All

Pagina 11

Created 03/04/2009 Edited and/or Printed 04/10/2014 282601 - 19 Project No. 44611-E 2. No grease, oil, or lubricant other than wire-pulling compoun

Pagina 12

Created 03/04/2009 Edited and/or Printed 04/10/2014 282601 - 2 Project No. 44611-E C. Company Field Advisor – An individual meeting the requirement

Pagina 13

Created 03/04/2009 Edited and/or Printed 04/10/2014 282601 - 20 Project No. 44611-E 2. Test all new cables prior to making final connections to con

Pagina 14

Created 03/04/2009 Edited and/or Printed 04/10/2014 282601 - 21 Project No. 44611-E D. Close Out submission 1. See Section 1.05 E & F for det

Pagina 15

Created 03/04/2009 Edited and/or Printed 04/10/2014 282601 - 22 Project No. 44611-E 9) Training should include precautionary concerns that personne

Pagina 16

Revised 11/19/2008 Edited and/or Printed 04/10/2014 283100 - 1 Project No. 44611-E SECTION 283100 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERA

Pagina 17

Revised 11/19/2008 Edited and/or Printed 04/10/2014 283100 - 2 Project No. 44611-E D. Provide and install devices, equipment and wiring as necessa

Pagina 18

Revised 11/19/2008 Edited and/or Printed 04/10/2014 283100 - 3 Project No. 44611-E O. All AC power supply conductors, remote signaling conductors,

Pagina 19

Revised 11/19/2008 Edited and/or Printed 04/10/2014 283100 - 4 Project No. 44611-E c. Alarm activation of any other elevator lobby smoke detector

Pagina 20

Revised 11/19/2008 Edited and/or Printed 04/10/2014 283100 - 5 Project No. 44611-E 3. System addressable devices shall be supervised for placement

Pagina 21

Revised 11/19/2008 Edited and/or Printed 04/10/2014 283100 - 6 Project No. 44611-E G. All system wiring shall be monitored for integrity in accord

Pagina 22

Revised 11/19/2008 Edited and/or Printed 04/10/2014 283100 - 7 Project No. 44611-E 2. All portions of the fire alarm systems, with the exception o

Pagina 23

Created 03/04/2009 Edited and/or Printed 04/10/2014 282601 - 3 Project No. 44611-E 10. Upon activation of an Alarm the system shall provide prepro

Pagina 24 - Revised 11/19/2008

Revised 11/19/2008 Edited and/or Printed 04/10/2014 283100 - 8 Project No. 44611-E 5. The system shall be designed and equipped to receive, monito

Pagina 25

Revised 11/19/2008 Edited and/or Printed 04/10/2014 283100 - 9 Project No. 44611-E T. Occupant Notification System – Buildings 6, 10, 11, 12 ,14 ,

Pagina 26

Revised 11/19/2008 Edited and/or Printed 04/10/2014 283100 - 10 Project No. 44611-E throughout all occupiable areas of the building. In no case sh

Pagina 27

Revised 11/19/2008 Edited and/or Printed 04/10/2014 283100 - 11 Project No. 44611-E V. Auxiliary Function Interfaces (Relays) 1. Auxiliary functi

Pagina 28

Revised 11/19/2008 Edited and/or Printed 04/10/2014 283100 - 12 Project No. 44611-E 2. 2975-9426 Three-Bay Beige Box with Glass Panel 3. 4100-230

Pagina 29

Revised 11/19/2008 Edited and/or Printed 04/10/2014 283100 - 13 Project No. 44611-E 3. 2081-9288 12.7 AH (two required) 4. 2081-9275, 18 AH (two

Pagina 30

Revised 11/19/2008 Edited and/or Printed 04/10/2014 283100 - 14 Project No. 44611-E 4. 2098-9798, for ducts from 46 to 71 inches wide 5. 2098-979

Pagina 31

Revised 11/19/2008 Edited and/or Printed 04/10/2014 283100 - 15 Project No. 44611-E E. If wall-mounted appliance is surface mounted, and industry-

Pagina 32

Revised 11/19/2008 Edited and/or Printed 04/10/2014 283100 - 16 Project No. 44611-E 2.17 SPEAKER-ONLY APPLIANCES A. Speaker only appliances shall

Pagina 33 - PART 2 - PRODUCTS

Revised 11/19/2008 Edited and/or Printed 04/10/2014 283100 - 17 Project No. 44611-E 2.19 REMOTE ALARM INDICATORS A. Each duct smoke detector, bea

Pagina 34

Created 03/04/2009 Edited and/or Printed 04/10/2014 282601 - 4 Project No. 44611-E C. Quality Control Submittals (Submittals Package 1): 1.

Pagina 35

Revised 11/19/2008 Edited and/or Printed 04/10/2014 283100 - 18 Project No. 44611-E 2.24 DOOR HOLDERS A. Where shown on the drawings, door holder

Pagina 36

Revised 11/19/2008 Edited and/or Printed 04/10/2014 283100 - 19 Project No. 44611-E 5. All new device backboxes, pull boxes and terminal cabinets

Pagina 37

Revised 11/19/2008 Edited and/or Printed 04/10/2014 283100 - 20 Project No. 44611-E G. Existing smoke, heat, and duct detectors which are to remai

Pagina 38

Created 03/04/2009 Edited and/or Printed 04/10/2014 282601 - 5 Project No. 44611-E minute minimum back-up time (Calculate a 2 hour backup if there i

Pagina 39

Created 03/04/2009 Edited and/or Printed 04/10/2014 282601 - 6 Project No. 44611-E completeness and approves all materials and installation methods

Pagina 40

Created 03/04/2009 Edited and/or Printed 04/10/2014 282601 - 7 Project No. 44611-E terminations and splices (identification shall correspond to mark

Pagina 41

Created 03/04/2009 Edited and/or Printed 04/10/2014 282601 - 8 Project No. 44611-E on termination, bonding and grounding procedures required for pro

Pagina 42

Created 03/04/2009 Edited and/or Printed 04/10/2014 282601 - 9 Project No. 44611-E 2.02 TRANSMITTERS (PROVIDED BY TYCO) A. All Transmitters shall

Comentarios a estos manuales

Sin comentarios